Fire alarms
Repeated false alarms — finding the cause instead of living with it
The system activates with no fire, repeatedly, and staff or tenants are ignoring it.
Book within days
Short answer
Persistent unwanted fire signals are a design or siting problem far more often than a faulty detector. The fix is usually relocating or re-specifying detectors in the affected area, not replacing the panel.

Start with a pattern, not a guess
Before changing hardware, we look for a pattern in the panel's event log. Activations clustered around breakfast service point at a kitchen; activations after showers point at steam migrating into a hallway detector; activations on windy nights point at dust disturbance in a roof void or a smoke seal problem.
The log usually names the exact device. That turns an open-ended complaint into a specific piece of work.
The usual causes in the buildings we cover
Across HMOs, pubs, care settings and small industrial units the recurring causes are:
- Optical smoke detectors sited too close to cooking, toasters or a bathroom door.
- Steam and aerosol use — hairspray and deodorant in bedsit-style rooms.
- Dust and insects inside the chamber, common in older detectors that have never been cleaned.
- Contractors working without the zone being isolated.
- Manual call points without protective covers in publicly accessible corridors.
What actually reduces them
Depending on the cause, the remedy is usually one of: relocating the detector outside the affected air path, swapping an optical for a heat or multi-sensor device where the fire risk assessment supports it, fitting call point covers, cleaning or replacing aged detectors, and introducing a formal contractor isolation procedure.
Where the system is being changed, the fire risk assessment should be reviewed so the detection coverage still matches the assessed risk. We handle both sides of that.
The compliance risk of doing nothing
The most serious consequence of chronic false alarms is not nuisance — it is habituation. Once occupants assume every sounder is a false alarm, evacuation times collapse. Fire and rescue services also record repeat unwanted signals from the same address, and some operate a charging policy for repeated attendance.
Questions we get asked about this
Should I disable the detector that keeps going off?
Only as a temporary, recorded measure with a compensating watch in place — and never as a long-term fix. A permanently disabled device leaves a gap in the detection coverage your fire risk assessment relies on.
Will changing to a multi-sensor detector fix it?
Often, where the trigger is steam or cooking aerosols. A multi-sensor requires corroborating signals before it alarms. It is not a universal cure — if the detector is simply in the wrong place, it needs moving.
Can you review the whole system rather than one device?
Yes. Where activations are spread across zones we would normally recommend a detection review alongside the fire risk assessment, so any change is justified in writing.
Send us your last three months of activations and we will tell you what we think is causing them before quoting.
Other common fire safety problems
Compliance & enforcement
Asked for a fire alarm certificate and you haven't got one
Fire doors
Fire door gaps that are too big — tolerances and remedies
Fire doors
Fire door won't close and latch — diagnosing the cause
Fire doors
Fire door with no intumescent seals — can it be retrofitted?
Need a Fire Risk Assessment?
Stay compliant and protect your premises. Get a free, no-obligation quote within 24 hours.